Rugged Online UPS with Input Power factor correction & Isolation Transformer with IGBT Module
TriVector Pfc Series of Online UPS using double conversion topology to provide clean and stable power supply to your Equipment’s. In This topology the current Draw from line also clean with very low THD. These UPS are 3 phase input and 1 phase output type, Extra ruggedness provided by Built in Isolation transformer. TriVector Pfc Series UPS provide better output power with high performance and efficiency for critical applications. The unique Eco Mode Provide up to 99% efficiency.
Configuration
- 3 Phase input , 1 Phase output


Main Features
- With Isolation Transformer Builtin and Transformer less model
- DSP technology guarantees high performance
- IGBT module for extra ruggedness
- Active Input power factor correction 0.99 with IGBT Rectifier
- True Double-conversion online UPS
- ECO mode operation for energy saving
- Generator compatible
- High overload capability and enhanced short circuit protection
- User-friendly and easy-shift LCD display
- SNMP/USB/RS-232 multiple communications
- 3-stage smart charging design
- Maximum 12A extended Charging
- Selectable output voltage: 200-240VAC
MODEL | TriVector pFC 10KVA | TriVector pFC 15KVA | TriVector pFC 20KVA | TriVector pFC 30KVA |
PHASE | 3-phase in / 1-phase out Ground and nutral | |||
Capacity | 10000 VA / 9000 W | 15000 VA / 13500 W | 20000 VA / 18000 W | 30000 VA / 27000 W |
INPUT PARAMETERS | ||||
Input Nominal Voltage | 3 x 400 VAC (3Ph+N) | |||
Input Voltage Range | 190-520 VAC (3-phase) @ 50% load ; 305-478 VAC (3-phase) @ 100% load | |||
Frequency Range | 45-55Hz or (55-65Hz)** | |||
Power Factor | ≥0.99 at Nominal Voltage 100% Load | |||
Harmonic Distortion(THDi) | ≤7% at full load with linear load | |||
OUTPUT PARAMETERS | ||||
Output Voltage | 208/220/230/240VAC | |||
Output Voltage Regulation | ±1 % | |||
Frequency Range (Batt. Mode) | 50Hz ±0.1 % or (60Hz ±0.1 %)** | |||
Frequency Range (Synchronized Mode) | 47 to 53 Hz or (57 to 63Hz)** | |||
Transfer Time | AC to Battery 0 ms, Inverter to Bypass 0 ms typical | |||
Waveform | Pure Sine wave | |||
Current Crest Ratio | 3:1 | |||
Total Harmonic Distortion (THDu) | ≤2% THD(Linear Load), ≤5% THD(Non Linear Load) | |||
Over Load ( Run On AC Line *) | 100 ~ 110%: 10 Min; 110 ~ 130%: 1 Min; > 130%: 1 Sec | |||
Over Load ( Battery Mode) | 100 ~ 110%: 30 Sec; 110 ~ 130%: 10 Sec; > 130%: 1 Sec | |||
EFFECIEANCY | ||||
Battery Mode | 91.5% | 91.8% | 91.8% | 92.1% |
Eco Mode | 97% | 97% | 97% | 97% |
AC Mode | 87% | 88% | 88% | 89% |
BATTERY | ||||
Battery Numbers | 20 pcs (18 - 20 pcs adjustable)* | |||
Battery Float Charging Voltage | 273 VDC (Based on batteries of 20 Nos.) | |||
Max Charging Current External Battery Model | 4A | 8A | 8A | 12A |
Max Charging Current Internal 7Ah 12V Batteries Model | 1A | 2A | 2A | 4A |
Internal 7Ah 12V Batteries Recharge Time | 9 Hrs up 90% Charged | 9 Hrs up 90% Charged | ||
INDICATORS on LED & LCD | ||||
Ups Status, Load Level, Battery Level, Input /Output Voltage, Discharge Time, And Fault Alarm | ||||
ALARM | ||||
Battery Mode | Beep Every 5 Seconds | |||
Low Battery Alarm | Beep Every 2 Seconds | |||
Over Load Alarm | Beep Every 1 Seconds | |||
Fatal Fault/Error | Continuous Beep | |||
ENVIRONMENTAL | ||||
Operating Humidity and Temperature | 0-95% RH Non Condensing at 0-40 ℃ | |||
Noise Level | ≤ 58 dB @ 1Mtrs. | ≤ 60 dB @ 1Mtrs. | ||
COMmUNICATION | ||||
Optional SNMP | Remote Management Via SNMP and Web Browser | |||
RS-232 Com Port / USB | Support all window Linux and Mac Optional Monitoring Software via 3rd party software | |||
*When using internal batteries from 18-19, the unit will de-rate according to below formula: P = PRating x N/20. **110V, 60Hz Voltage and Frequency Converter Mode with optional step down output transformer @Regulation 3% #We take utmost care to make specification however crosscheck before ordering for specifications ##Due to continuous development The specification may be changed so crosscheck before ordering |