Rugged Online UPS with Input Power Factor Correction and Isolation Transformer with IGBT Module
The TriVector PFC Series of online UPSes uses a double conversion topology to provide a clean and stable power supply to your equipment. In this topology, the current draw from the line is also clean with very low THD. These UPS have 3-phase input and 1-phase output types. Extra ruggedness is provided by the built-in isolation transformer. TriVector PFC Series UPS provide better output power with high performance and efficiency for critical applications. The unique Eco Mode provides up to 99% efficiency.
Configuration
- 3 phase input, 1 phase output
Main Features
- With Isolation Transformer Builtin and Transformer less model
- DSP technology guarantees high performance
- IGBT module for extra ruggedness
- Active Input power factor correction 0.99 with IGBT Rectifier
- True Double-conversion online UPS
- ECO mode operation for energy saving
- Generator compatible
- High overload capability and enhanced short circuit protection
- User-friendly and easy-shift LCD display
- SNMP/USB/RS-232 multiple communications
- 3-stage smart charging design
- Maximum 12A extended Charging
- Selectable output voltage: 200-240VAC
MODEL | TriVector pFC 10KVA | TriVector pFC 15KVA | TriVector pFC 20KVA | TriVector pFC 30KVA |
PHASE | 3-phase in / 1-phase out Ground and nutral | |||
Capacity | 10000 VA / 9000 W | 15000 VA / 13500 W | 20000 VA / 18000 W | 30000 VA / 27000 W |
INPUT PARAMETERS | ||||
Input Nominal Voltage | 3 x 400 VAC (3Ph+N) | |||
Input Voltage Range | 190-520 VAC (3-phase) @ 50% load ; 305-478 VAC (3-phase) @ 100% load | |||
Frequency Range | 45-55Hz or (55-65Hz)** | |||
Power Factor | ≥0.99 at Nominal Voltage 100% Load | |||
Harmonic Distortion(THDi) | ≤7% at full load with linear load | |||
OUTPUT PARAMETERS | ||||
Output Voltage | 208/220/230/240VAC | |||
Output Voltage Regulation | ±1 % | |||
Frequency Range (Batt. Mode) | 50Hz ±0.1 % or (60Hz ±0.1 %)** | |||
Frequency Range (Synchronized Mode) | 47 to 53 Hz or (57 to 63Hz)** | |||
Transfer Time | AC to Battery 0 ms, Inverter to Bypass 0 ms typical | |||
Waveform | Pure Sine wave | |||
Current Crest Ratio | 3:1 | |||
Total Harmonic Distortion (THDu) | ≤2% THD(Linear Load), ≤5% THD(Non Linear Load) | |||
Over Load ( Run On AC Line *) | 100 ~ 110%: 10 Min; 110 ~ 130%: 1 Min; > 130%: 1 Sec | |||
Over Load ( Battery Mode) | 100 ~ 110%: 30 Sec; 110 ~ 130%: 10 Sec; > 130%: 1 Sec | |||
EFFECIEANCY | ||||
Battery Mode | 91.5% | 91.8% | 91.8% | 92.1% |
Eco Mode | 97% | 97% | 97% | 97% |
AC Mode | 87% | 88% | 88% | 89% |
BATTERY | ||||
Battery Numbers | 20 pcs (18 - 20 pcs adjustable)* | |||
Battery Float Charging Voltage | 273 VDC (Based on batteries of 20 Nos.) | |||
Max Charging Current External Battery Model | 4A | 8A | 8A | 12A |
Max Charging Current Internal 7Ah 12V Batteries Model | 1A | 2A | 2A | 4A |
Internal 7Ah 12V Batteries Recharge Time | 9 Hrs up 90% Charged | 9 Hrs up 90% Charged | ||
INDICATORS on LED & LCD | ||||
Ups Status, Load Level, Battery Level, Input /Output Voltage, Discharge Time, And Fault Alarm | ||||
ALARM | ||||
Battery Mode | Beep Every 5 Seconds | |||
Low Battery Alarm | Beep Every 2 Seconds | |||
Over Load Alarm | Beep Every 1 Seconds | |||
Fatal Fault/Error | Continuous Beep | |||
ENVIRONMENTAL | ||||
Operating Humidity and Temperature | 0-95% RH Non Condensing at 0-40 ℃ | |||
Noise Level | ≤ 58 dB @ 1Mtrs. | ≤ 60 dB @ 1Mtrs. | ||
COMmUNICATION | ||||
Optional SNMP | Remote Management Via SNMP and Web Browser | |||
RS-232 Com Port / USB | Support all window Linux and Mac Optional Monitoring Software via 3rd party software | |||
*When using internal batteries from 18-19, the unit will de-rate according to below formula: P = PRating x N/20. **110V, 60Hz Voltage and Frequency Converter Mode with optional step down output transformer @Regulation 3% #We take utmost care to make specification however crosscheck before ordering for specifications ##Due to continuous development The specification may be changed so crosscheck before ordering |