Rugged Online UPS with Isolation Transformer and IGBT Module
Polense S Series of Online UPS using double conversion topology to provide clean and stable power supply to your Equipment’s. These UPS are 3 phase input and 1 phase output type, With Built in Isolation transformer Provide extra ruggedness to the equipment run on UPS. Polense S Series UPS provide better output power with high performance and efficiency for critical applications. The unique Eco Mode Provide up to 99% efficiency.
Configuration
- 3 Phase input , 1 Phase output
Main Features
- Isolation Transformer Builtin
- IGBT module for extra ruggedness
- True Double-conversion online UPS
- 3 Phase Input and 1 Phase Output
- ECO mode operation for energy saving
- Generator compatible
- High overload capability and enhanced short circuit protection
- SNMP/USB/RS-232 multiple communications
- 3-stage smart charging design
- Maximum 12A extended Charging
- Selectable output voltage: 200-240VAC
MODEL | Polense J 3KVA To 10KVA | Polense S 10KVA To 30KVA | ||
PHASE | Single Phase Input and Single Phase Output With Ground | Three Phase Input and Single Phase Output With Nutral & Ground | ||
Capacity KVA/KW | 3.0/2.4, 5.0/4.8, 6.0/4.8, 7.5/6.0, 10.0/8.0 | 10.0/8.0, 15.0/12.0, 20.0/16.0, 30.0/24.0 | ||
INPUT PARAMETERS | ||||
Input Voltage Range at 50% load | 170-280VAC ±3% neutral to phase | 300-460VAC ±3% phase to phase | ||
Input Voltage Range at 100% load | 210-260VAC ±3% neutral to phase | 360-440VAC ±3% phase to phase | ||
Nominal Voltage | 230V ±3% neutral to phase | 400VAC ±3% phase to phase | ||
Frequency Range | 45-55Hz | |||
OUTPUT PARAMETERS | ||||
Output Voltage | 200/208/220/230/240 VAC SETTABLE | |||
Output Voltage Regulation | ±1 % | |||
Frequency Range (Batt. Mode) | 50Hz ±0.1 % | |||
Frequency Range (Synchronized Mode) | 47 to 53 Hz | |||
Transfer Time | AC to Battery 0 ms, Inverter to Bypass 4 ms typical | |||
Waveform | Pure Sine wave | |||
Current Crest Ration | 3:1 | |||
Total Harmonic Distortion (THDu) | ≤2% THD(Linear Load), ≤5% THD(Non Linear Load) | |||
Over Load | 100 ~ 110%: 30 Sec; 110 ~ 130%: 10 Sec; > 130%: 1 Sec | |||
EFFECIEANCY | ||||
Battery Mode | ≥0.80% | ≥0.82% | ||
Eco Mode | ≥0.97% | |||
AC Mode | ≥0.78% | ≥0.80% | ||
BATTERY | ||||
Battery Numbers KVA/Nos | 3KVA/12, 5KVA/12, or 5KVA/15, 6KVA/16, 7.5KVA/16 | 10KVA/20, 15KVA/30 20KVA/30, 30KVA/30, or 30KVA/32 | ||
Battery Charging Voltage | 13.8V MULTIPLIED BY NUMBERS OF BATTRIES | |||
Max Charging Current | 3 TO 12 Amps Settable | |||
Battery Capacity | Up to 65 Ah | |||
INDICATORS on LED & LCD | ||||
Ups Status, Load Level, Battery Level, Input /Output Voltage, Discharge Time, And Fault Alarm | ||||
ALARM | ||||
Battery Mode | Beep Every 5 Seconds | |||
Low Battery Alarm | Beep Every 2 Seconds | |||
Over Load Alarm | Beep Every 1 Seconds | |||
Fatal Fault/Error | Continuous Beep | |||
ENVIRONMENTAL | ||||
Operating Humidity and Temperature | 20-95% RH Non Condensing at 0-40 ℃ | |||
Noise Level | ≤ 50 dB @ 1Mtrs. | |||
COMMUNICATION | ||||
Optional SNMP | Remote Management Via SNMP and Web Browser | |||
RS-232 Com Port / USB | Support all window Linux and Mac Optional Monitoring Software via 3rd party software | |||
#We take utmost care to make specification however crosscheck before ordering for specifications ##Due to continuous development The specification may be changed so crosscheck before ordering |