Mega iND II is a rugged online UPS suitable for industrial and facility applications.
Configuration
- 3 phase input, 3 phase output, neutral
Applications
- Industrial processes (manufacturing and control systems, industrial machinery, instrumentation and measurement, process monitoring and control, security and transport systems, etc.)
- Infrastructures (hospital, airport, semiconductor, water treatment, power plant, metallurgy)
- Energy industry (gas and oil, petrochemicals, mining)
- Military application
Main Features
- Industrial Grade Enclosure with front access of all electronics.
- IP31-rated protection, this UPS is allowed for side-by-side operation against the wall.
- Dust Filters On FAN
- To guarantee continuous operation of the product in harsh environment, MEGA iND II is designed with redundant power supply. Margin design is applied to internal key components to ensure safety operation.
- Up to 4 units in parallel can be operated without adding additional hardware, increasing system capacity as well as operation reliability for power redundancy.
- Temperature compensation to prolong battery life
- Backfeed protection and in-built 40kA surge protection guarantee safety operation
- Isolation Transformer Built-in
- IGBT module for extra ruggedness
- True Double-conversion online UPS
- High overload capability and enhanced short circuit protection
- SNMP/USB/RS-232 multiple communications
MODEL | MEGA iND II 10KVA | MEGA iND II 20KVA | MEGA iND II 30KVA | MEGA iND II 40KVA | MEGA iND II 60KVA | MEGA iND II 80KVA | MEGA iND II 100KVA | MEGA iND II 120KVA | MEGA iND II 160KVA |
PHASE | 3-phase in / 1-phase out Ground and nutral | ||||||||
Capacity | 10KVA/ | 20KVA/ | 30KVA/ | 40KVA/ | 60KVA/ | 80KVA/ | 100KVA/ | 120KVA/ | 160KVA/ |
INPUT PARAMETERS | |||||||||
Rectifier Type | 6 Pulse (12 Pulse or Harmonic Filter Optional) | ||||||||
Main Input and Bypass Input | Supports Separate inputs for Mains and Bypass | ||||||||
TVSS | 40KA | ||||||||
Input Nominal Voltage | 380VAC/400VAC/415VAC 3 Phase without Neutral | ||||||||
Input Voltage Range | 304VAC ~ 456VAC | ||||||||
Frequency Range | 50Hz/60Hz ± 10% | ||||||||
BYPASS | |||||||||
Nominal Voltage | 380VAC/400VAC/415VAC | ||||||||
Input Voltage Range | 285VAC ~ 475VAC | ||||||||
Transfer Time | 0 | ||||||||
OUTPUT PARAMETERS | |||||||||
Output Voltage | 380VAC/400VAC/415VAC 3 Phase with Neutral | ||||||||
Output Voltage Regulation | 1% | ||||||||
Frequency | 50Hz/60Hz ± 1% | ||||||||
Power Factor | 0.8 to 0.99 | ||||||||
Waveform | Pure Sine wave | ||||||||
Current Crest Ratio | 3:1 | ||||||||
Total Harmonic Distortion (THDu) | ≤2% THD(Linear Load), ≤5% THD(Non Linear Load) | ||||||||
Over Load Capacity | 110% continuous running; 125% for 10 min; >150% for 1 min | ||||||||
EFFECIEANCY | |||||||||
Battery Mode | 91.5% | ||||||||
AC Mode | 87% | ||||||||
BATTERY | |||||||||
Battery Numbers | 384VDC or 192Nos. 2V Cells (Number of Cells Adjustable) | ||||||||
Battery Float Charging Voltage | 13.8V, Adjustable from 13.4V to 14.0 | ||||||||
Battery Boost Charging Voltage | 14.2V, Adjustable from 13.8V to 14.6 | ||||||||
Charging Current | 10A, Adjustable from 5A to 30A | ||||||||
Cold Start | Yes | ||||||||
INDICATORS on LED & Graphic LCD | |||||||||
Ups Status, Load Level, Battery Level, Input /Output Voltage, Discharge Time, And Fault Alarm | |||||||||
ALARM | |||||||||
Low Battery Alarm | Beep Every 2 Seconds / Mutable | ||||||||
Over Load Alarm | Beep Every 1 Seconds / Mutable | ||||||||
Fatal Fault/Error | Continuous Beep / Mutable | ||||||||
ENVIRONMENTAL | |||||||||
Operating Humidity and Temperature | 0-95% RH Non Condensing at 0-40 ℃ | ||||||||
Noise Level | ≤ 65 dB @ 1Mtrs. | ||||||||
COMMUNICATION | |||||||||
Optional SNMP | Remote Management Via SNMP and Web Browser | ||||||||
Dry Contacts | 5 outputs and 4 inputs | ||||||||
RS-232 Com Port / USB | Support all window Linux and Mac Optional Monitoring Software via 3rd party software | ||||||||