WIDE INPUT RANGE UPS WITH 0.99 POWER FACTOR
The Orion PFC H Series of online UPS uses triple conversion topology to provide a clean and stable power supply to your equipment. In this topology, the current draw from the line is also clean with very low THD. These UPS are 1 or 3-phase input and 1-phase output types. An optional built-in isolation transformer may be provided if ordered. The Orion PFC H Series UPS provides better output power with high performance and efficiency for critical applications. The unique Eco Mode provides up to 99% efficiency.
Configuration
- 1 phase input, 1 phase output
Applications
- Datacenters, industrial machinery, instrumentation and measurement, process monitoring and control, security and transport systems, etc.
- hospital, airport, OT’s
- Superstore, CCTV, Flex Banner Printing Machines, etc.
Main Features
- True Double-conversion online UPS
- DSP technology guarantees high performance
- Rack/Tower design
- User-friendly and easy-shift LCD display
- Wide input voltage range (100-300 VAC)
- 50Hz/60Hz frequency converter mode
- Active Input power factor correction 0.99
- Output power factor 0.9
- 50/60 Hz Frequency Converter Mode
- Emergency power off function (EPO)
- ECO mode operation for energy saving
- Generator compatible
- High overload capability and enhanced short circuit protection
- SNMP/USB/RS-232 multiple communications
- 3-stage smart charging design
- Maximum 5A extended Charging available for long run model
- Selectable output voltage: 200-240VAC
- Laser printer and ultrasound system load acceptable
- Isolation transformer is available as option
MODEL | ORION Pfc H 6KVA | ORION Pfc H 10KVA | ||
PHASE | Single Phase Input and Single Phase Output With Ground | |||
Capacity | 6000 VA 5400W | 10000VA 9000W | ||
INPUT PARAMETERS | ||||
Input Voltage Range at 50% load | 110- 300VAC ±5 % | |||
Input Voltage Range at 100% load | 175- 300VAC ±5 % | |||
Nominal Voltage | 200/208/220/230/240 VAC | |||
Frequency Range | 45-55Hz or (55-65Hz)** | |||
Power Factor | ≥0.99 at Nominal Voltage 100% Load | |||
Harmonic Distortion(THDi) | ≤7% at full load with linear load and battery fully charged | |||
OUTPUT PARAMETERS | ||||
Output Voltage | 200/208/220/230/240 VAC or (100/110/115/120/127 VAC)** | |||
Output Voltage Regulation | ±1 %, (±3 %)** | |||
Frequency Range (Batt. Mode) | 50Hz ±0.1 % or (60Hz ±0.1 %)** | |||
Frequency Range (Synchronized Mode) | 47 to 53 Hz or (57 to 63Hz)** | |||
Transfer Time | AC to Battery 0 ms, Inverter to Bypass 0 ms typical | |||
Waveform | Pure Sine wave on inverter | |||
Current Crest Ration | 3:1 | |||
Total Harmonic Distortion (THDu) | ≤2% THD(Linear Load), ≤5% THD(Non Linear Load) or ≤4% THD(Linear Load)**, ≤7% THD(Non Linear Load)** | |||
Over Load ( Run On AC Line *) | 100 ~ 110%: 10 Min; 110 ~ 130%: 1 Min; > 130%: 1 Sec | |||
Over Load ( Battery Mode) | 100 ~ 110%: 30 Sec; 110 ~ 130%: 10 Sec; > 130%: 1 Sec | |||
EFFECIEANCY | ||||
Battery Mode | ≥0.88% or (≥0.82%)** | |||
Eco Mode | ≥0.96% or (≥0.87%)** | |||
AC Mode | ≥0.91% or (≥0.85%)** | |||
BATTERY | ||||
Battery Numbers | 18-20 Nos. 12V | |||
Battery Float Charging Voltage | 273 VDC (Based on batteries of 20 Nos.) | |||
Long Run Model (External Battery Connections) Max Charging Current | 4 Amps Selectable | |||
Long Run Model (External Battery Connections) Battery Capacity | Up to 100 Ah | |||
Standard Model (Internal 7Ah 12V Batteries) Max Charging Current | 1.0 Amps | |||
Standard Model (Internal 7Ah 12V Batteries) Internal Battery Recharge Time | 7 Hrs up 90% Charged | 9 Hrs up 90% Charged | ||
INDICATORS on LED & LCD | ||||
Ups Status, Load Level, Battery Level, Input /Output Voltage, Discharge Time, And Fault Alarm | ||||
ALARM | ||||
Battery Mode | Beep Every 5 Seconds | |||
Low Battery Alarm | Beep Every 2 Seconds | |||
Over Load Alarm | Beep Every 1 Seconds | |||
Fatal Fault/Error | Continuous Beep | |||
ENVIRONMENTAL | ||||
Operating Humidity and Temperature | 0-95% RH Non Condensing at 0-40 ℃ | |||
Noise Level | ≤ 58 dB @ 1Mtrs. | ≤ 60 dB @ 1Mtrs. | ||
COMmUNICATION | ||||
Optional SNMP | Remote Management Via SNMP and Web Browser | |||
RS-232 Com Port / USB | Support all window Linux and Mac Optional Monitoring Software via 3rd party software | |||
*Capacity and Current handling of UPS degraded On Low Line Voltage **110V, 60Hz Voltage and Frequency Converter Mode with optional step down output transformer @Regulation 3% #We take utmost care to make specification however crosscheck before ordering for specifications ##Due to continuous development The specification may be changed so crosscheck before ordering |